Volume discount: 5 pcs 2% · 10 pcs 3% · 25 pcs 5%When two hands measure the same bore differently: How three measuring points eliminate operator errorWhen the Bore Has to Be Measured Right: How a Self-Centering Three-Point Micrometer Removes Operator UncertaintyThree measuring points give a bore diameter that doesn’t depend on who is measuringWhen the multimeter shows 90 volts on a disconnected cable: how to tell ghost voltage from the real thingRead the tolerance in seconds when the micrometer shows the deviation directlySmall holes are rarely measured correctly with two points: how three contact points give you a diameter result you can trustYour measurement is never better than the surface you measure againstHow to Measure Ground Resistance Without Disconnecting the Ground Connection and Without Ground StakesSurface temperature reads incorrectly if the emissivity doesn’t match the materialWhen the Bore Looks Round but the Measurement Still Misleads: How Three Contact Points Give You a Number You Can TrustVolume discount: 5 pcs 2% · 10 pcs 3% · 25 pcs 5%When two hands measure the same bore differently: How three measuring points eliminate operator errorWhen the Bore Has to Be Measured Right: How a Self-Centering Three-Point Micrometer Removes Operator UncertaintyThree measuring points give a bore diameter that doesn’t depend on who is measuringWhen the multimeter shows 90 volts on a disconnected cable: how to tell ghost voltage from the real thingRead the tolerance in seconds when the micrometer shows the deviation directlySmall holes are rarely measured correctly with two points: how three contact points give you a diameter result you can trustYour measurement is never better than the surface you measure againstHow to Measure Ground Resistance Without Disconnecting the Ground Connection and Without Ground StakesSurface temperature reads incorrectly if the emissivity doesn’t match the materialWhen the Bore Looks Round but the Measurement Still Misleads: How Three Contact Points Give You a Number You Can Trust

How to Measure Ground Resistance Without Disconnecting the Ground Connection and Without Ground Stakes

Published 12 November 2026 at 07:20

Most people who have worked on an installation know the classic ground measurement: the grounding conductor is disconnected, two auxiliary stakes are driven into the ground at a specified distance, leads are rolled out, and the system often has to be taken out of operation while it is carried out. If the ground surface is paved or there is no room for stakes, the measurement is either postponed or abandoned altogether. As a result, in practice ground connections are checked less often than they should be.

Ground måler med sporbart kalibreringscertifikat

What is a clamp-type ground tester

It is a clamp-shaped instrument that closes around the grounding conductor and measures the resistance of the ground loop without touching the conductor itself. There is no disconnection and no ground stakes. This instrument has a jaw opening of 23 mm and measures ground resistance from 0.025 to 1500 ohms with automatic ranging. It can also measure AC leakage current (TRMS) from 0.2 mA up to 30 A, so the same clamp can be used both to find a poor ground connection and to trace a leakage current.

What problems does it solve

It removes the biggest barrier to regular checks: the hassle. The measurement takes seconds, and the system can stay in operation. A programmable high/low alarm immediately shows whether the value is outside the limit, and 116 data points can be logged for documentation, so you do not have to write values down by hand.

The method requires the grounding conductor to be part of a closed loop, for example in a system with several parallel ground connections. With a single, stand-alone ground electrode without a return path, the clamp does not give a usable result, and the traditional method is still necessary.

Where is it used in practice

Manufacturing companies: Maintenance staff can check ground connections on machines, panels and rails during scheduled service without stopping the line, and compare values from year to year to detect corrosion or loose connections.

Electrical installation and panel building: At handover or periodic inspection, the installer can quickly check many grounding conductors and log the results for the report.

Food and process industry: In damp and washed-down environments, ground connections are exposed to corrosion. The leakage current function helps locate a motor or heating element where the insulation has begun to fail, before it triggers a fault current or causes a stoppage.

Why it pays off

The gain lies in the time not spent disconnecting, driving in stakes and rolling out leads, and in the downtime that is avoided. A measurement that used to require two people and a planned shutdown can now be handled by one person during normal operation. This means more points are actually measured, and faults are detected as a gradual increase in resistance rather than as an incident. The instrument comes with a traceable calibration certificate, which is an advantage if the measurements are part of a quality system or an audit. Please note that the delivery time for products with a traceable certificate is five weeks.

If you are putting off ground measurements today because the method is cumbersome, this is where you can see the specifications and order.