Volume discount: 5 pcs 2% · 10 pcs 3% · 25 pcs 5%When the Hole Is 500 mm Deep, the Measuring Instrument Has to Keep UpSee why the drain is blocked before you tear up the floor: a camera on five meters of cableWhen two hands measure the same bore differently: How three measuring points eliminate operator errorWhen the Bore Has to Be Measured Right: How a Self-Centering Three-Point Micrometer Removes Operator UncertaintyThree measuring points give a bore diameter that doesn’t depend on who is measuringWhen the multimeter shows 90 volts on a disconnected cable: how to tell ghost voltage from the real thingRead the tolerance in seconds when the micrometer shows the deviation directlySmall holes are rarely measured correctly with two points: how three contact points give you a diameter result you can trustYour measurement is never better than the surface you measure againstHow to Measure Ground Resistance Without Disconnecting the Ground Connection and Without Ground StakesVolume discount: 5 pcs 2% · 10 pcs 3% · 25 pcs 5%When the Hole Is 500 mm Deep, the Measuring Instrument Has to Keep UpSee why the drain is blocked before you tear up the floor: a camera on five meters of cableWhen two hands measure the same bore differently: How three measuring points eliminate operator errorWhen the Bore Has to Be Measured Right: How a Self-Centering Three-Point Micrometer Removes Operator UncertaintyThree measuring points give a bore diameter that doesn’t depend on who is measuringWhen the multimeter shows 90 volts on a disconnected cable: how to tell ghost voltage from the real thingRead the tolerance in seconds when the micrometer shows the deviation directlySmall holes are rarely measured correctly with two points: how three contact points give you a diameter result you can trustYour measurement is never better than the surface you measure againstHow to Measure Ground Resistance Without Disconnecting the Ground Connection and Without Ground Stakes

When the multimeter shows 90 volts on a disconnected cable: how to tell ghost voltage from the real thing

Published 16 November 2026 at 11:31

You are measuring on a disconnected circuit in a switchgear room, and the multimeter shows 90 V. You know the fuse has been removed, yet you don’t trust the number. Or worse: you measure 0 V on something that later turns out to be live. Both happen when a high-impedance instrument picks up capacitive coupling from neighboring cables, or when an RMS value is calculated incorrectly on a distorted waveform.

Cat IV sand RMS multimeter + Nettoproduktion under jorden og loz

What is the Extech EX360

The EX360 is a CAT IV-rated digital multimeter with true RMS for AC, a backlit 6000-count display and a fast analog bargraph that shows trends while you measure. It can also measure frequency and capacitance. The most important features, however, are the LoZ function (low impedance) and the built-in non-contact voltage detector.

What problems does it solve

In LoZ mode, the multimeter loads the circuit enough for ghost voltages to collapse. A genuine supply voltage does not disappear, so the reading is far more trustworthy when you need to determine whether a conductor is dead. True RMS gives correct values on loads that are not pure sine waves, for example switch-mode power supplies and frequency converters. Smart Data Hold freezes the value and warns with sound and light if the measurement changes by more than 50 counts. This is useful when you are in an awkward position and cannot keep an eye on the display. Peak Hold captures the highest value, and relative mode zeroes capacitance measurements.

When and why is it used

Use it for verifying absence of voltage, troubleshooting in switchboards and confirming supply before you start a job. The non-contact detector with Hi/Low range gives a quick first indication, and the multimeter then provides the actual answer. Note that LoZ should not be used on sensitive electronics, where the low impedance can load the circuit.

Practical examples

Maintenance in production: A motor circuit with long cables in the same cable tray as other circuits shows voltage even though it is disconnected. With LoZ, the technician can see whether it is a case of coupling or a genuine fault.

Installation in buildings: When inspecting existing installations where the wiring is not always documented, the combination of detector, LoZ and continuity test with visual alarm provides quick and systematic clarification.

Electronics and drive systems: When measuring at the output of a frequency converter, true RMS gives a realistic value where an average-responding instrument would read too low.

The economic argument

The most expensive measurement is the one you have to repeat, or the one that sends a technician off looking for a fault that does not exist. Misinterpreted ghost voltages cost hours, and incorrect readings on converter outputs can lead to unnecessary component replacements. An instrument that combines LoZ, true RMS, a detector and a magnetic hanger with a tilt function in a single case replaces several devices in the toolbox and provides a more secure basis for decisions.

See the specifications and scope of delivery for the Extech EX360 and assess whether it suits your maintenance tasks.